WIRE IS SECURELY CAPED.
AND COULD DAMAGE THE CONTROL.
Figure 2-1: Connection Wiring Directly to
Central Heating Circulator
Figure 2-2: Connection Wiring without Wiring
Central Heating Circulator
Note to Electrical Contractor: The orange
wire is 120 Volt/4 Amp maximum for central
heating circulator only. Loads greater than 4
amps or 3 amps for HA models only will blow the
fuse on the board. The brown wire is the neu-
tral wire for the central heating pump only.
Figure 2-3: For circulator amp loads greater
than 4 amps (3 amps for “HA” models) use the
wiring diagram shown at left. The brown and
orange wires will not be used in this
application.